Shelly PRO 3EM (120A or 400A)
$269.00 – $419.00
Shelly PRO 3EM is a professional DIN rail mountable three-phase energy meter. Enhanced with all the Shelly gen2 firmware flexibility and LAN connectivity, it can work standalone in a local LAN and/or Wi-Fi network. The Shelly PRO 3EM reports accumulated energy as well as instantaneous voltage, current, active and apparent power per phase in real time. It stores data in non-volatile memory that can be retrieved for a period of up to 60 days in 1-minute intervals. 3 x 120A or 400A clamps included (one for each phase).
FREE EXTENDED WARRANTY
SMARTHOME REWARD POINTS
FAST DELIVERY - FREE OVER $199
SHELLY PRO 3EM.
Professional 3-phase energy monitoring.
4-quadrant measurement
High accuracy
MODBUS support
Wi-Fi, LAN, and Bluetooth
Power monitoring
Monitors mono-phase electrical systems with up to 3 points simultaneously. Fast notifications and 60 days record storage.
Scripting functionalities
Shelly Pro 3EM fully supports mjS scripting, allowing you to create further features, functionalities and interoperability.
Shelly 3EM PRO 120A
Monitor loads up to 120A per phase (clamps suitable for active cables up to 16mm in diameter).
Shelly 3EM PRO 400A
Monitor loads up to 400A per phase (clamps suitable for active cables up to 35mm in diameter).
Industry-grade security.
Thanks to Shelly Pro 3EM’s scripting functionalities and webhooks, you can now easily control other Shelly or Wi-Fi devices on your local network. Use these capabilities to set exact parameters for HVAC, pool pumps, electric vehicle charging, etc – based on solar production. All without using “the cloud”.
Energy monitoring.
The finer details
Physical | |
Size (HxWxD): | 94x19x69 ±0.5 mm |
Weight: | 62 ±1 g |
Mounting: | DIN rail |
Screw terminals max torque: | 0.4 Nm / 4.43 lbin |
Conductor cross section: | 0.5 to 2.5 mm² / 20 to 14 AWG (solid, stranded and bootlace lugs) |
Conductor stripped length: | 6 to 7 mm / 0.24 to 0.28 in |
Environmental | |
Ambient temperature: | -20 °C to 40 °C / -5 °F to 105 °F |
Humidity: | 30 % to 70 % RH |
Max. altitude: | 2000 m / 6562 ft |
Electrical | |
Power supply voltage AC: | 110 - 240 V, 50/60 Hz |
Power supply DC: | No |
Device power consumption: | < 3 W |
Monitoring clamps: | Includes 3 x CT120 (120A) clamps or 3 x CT400 (400A) clamps |
Sensors & Meters | |
Temperature sensor: | Yes |
Voltmeters (RMS for each phase): | 100 - 260 V |
Voltmeters accuracy: | ±1 % |
Ammeters (RMS via CT for each phase and the Neutral): | 0 - 120 A |
Ammeters accuracy: | ±1 % (2 - 120 A), ±2 % (1 - 2 A), ±5 % (0 - 1 A) |
Power and energy meters: | Active and apparent power; Active and apparent energy; Power factor; Fundamental active and fundamental reactive energy |
Measurement data storage: | At least 60 days of 1 min data resolution |
Data export: | CSV for PQ recorded values, JSON format export trough RPC |
Radio & Data | |
Wi-Fi protocol: | 802.11 b/g/n |
Wi-Fi Band: | 2401 - 2495 MHz |
Wi-Fi signal power: | <20 dBm |
Wireless range: | Up to 50 m outdoors and up to 30 m indoors (depending on the building materials) |
Bluetooth Protocol: | 4.2 |
Bluetooth Range: | Up to 10 m / 33 ft indoors and 30 m / 100 ft outdoors |
Ethernet: | 1 x RJ45 Ethernet socket |
MCU | |
CPU: | ESP32-D0WDQ6 |
Flash memory: | 16 MB |
Firmware Capabilities | |
Webhooks (URL actions): | 20 with 5 URLs per hook |
Scripting: | mJS |
MQTT: | Yes |
CoAP: | No |
OPTIONAL ACCESSORIES
Shelly Wall Display
Shelly PRO 4 Port LAN Switch
FROM OUR BLOG
How to use Shelly Wall Display with Home Assistant
An introduction to Shelly Wi-Fi smart devices
Shelly wireless 2-way switch
How to create Shelly scenes and schedules
Shelly Wi-Fi Setup & Troubleshooting Guide
Free Shelly Quick Apps for Fibaro Home Center 3
Product Questions & Answers
- Is it possible to extent the length of cable on the 400a clamps without causing issues
- Q Is it possible to extent the length of cable on the 400a clamps without causing issuesA Yes - we have had electrician customers extend by up to 3m without issue. Is this only for 3 phase? As it shares neutral so couldn’t be used for multiple single phase as it would trip rcbos…
- Q Is this only for 3 phase? As it shares neutral so couldn’t be used for multiple single phase as i...... Read moreA This device is designed to be used on 3 phase or 3 circuits. Hi - are the clamps bi-directional for the Pro model?
- Q Hi - are the clamps bi-directional for the Pro model?A
No - they are uni-directional (one-way).
Has this product been certified for Australian use? - Q Has this product been certified for Australian use?A
Yes, all Shelly products we offer are fully approved for Australia and New Zealand.
Reviews
There are no reviews yet.